(6) Turn off the burner and remove the
thermocouple rake.
(7) Repeat (1) to ensure that the burner is
in the correct range.
(g)
Test Procedure.
(1) Mount a thermo-
couple of the same type as that used for cali-
bration at a distance of 4 inches (102 mm)
above the horizontal (ceiling) test specimen.
The thermocouple should be centered over
the burner cone.
(2) Mount the test specimen on the test
stand shown in Figure 1 in either the hori-
zontal or vertical position. Mount the insu-
lating material in the other position.
(3) Position the burner so that flames will
not impinge on the specimen, turn the burn-
er on, and allow it to run for 2 minutes. Ro-
tate the burner to apply the flame to the
specimen and simultaneously start the tim-
ing device.
(4) Expose the test specimen to the flame
for 5 minutes and then turn off the burner.
The test may be terminated earlier if flame
penetration is observed.
(5) When testing ceiling liner panels,
record the peak temperature measured 4
inches above the sample.
(6) Record the time at which flame pene-
tration occurs if applicable.
(h)
Test Report.
The test report must in-
clude the following:
(1) A complete description of the materials
tested including type, manufacturer, thick-
ness, and other appropriate data.
(2) Observations of the behavior of the test
specimens during flame exposure such as
delamination, resin ignition, smoke, ect., in-
cluding the time of such occurrence.
(3) The time at which flame penetration
occurs, if applicable, for each of the three
specimens tested.
(4) Panel orientation (ceiling or sidewall).