Pt. 25, App. F 14 CFR Ch. I (1-1-19 Edition) spaschal on DSK3GDR082PROD with CFR (ii) Calorimeter. The calorimeter must be a total heat flux, foil type Gardon Gage of an appropriate range such as 0-20 Btu/ft 2-sec (0- 22.7 W/cm 2), accurate to Section3% of the indicated reading. The heat flux calibration method must be in accordance with paragraph VI(b)(7) of this appendix. (iii) Calorimeter mounting. Mount the calorimeter in a 6- by 12- Section0.125 inch (152- by 305- Section3 mm) by 0.75 Section0.125 inch (19 mm Section3 mm) thick insulating block which is attached to the heat flux calibration rig during calibration (figure 4). Monitor the insulating block for deterioration and replace it when necessary. Adjust the mounting as necessary to ensure that the calorimeter face is parallel to the exit plane of the test burner cone. 434 VerDate Sep<11>2014 12:50 Apr 30, 2019 Jkt 247046 PO 00000 Frm 00444 Fmt 8010 Sfmt 8002 Y:\SGML\247046.XXX 247046